24kv Indoor Medium Voltage Side Installation Type Vacuum Circuit Breaker

24kv Indoor Medium Voltage Side Installation Type Vacuum Circuit Breaker

Overview Package Size 96.00cm * 31.00cm * 70.00cm Package Gross Weight 120.000kg Lead Time 3 days (1 - 1 pcs) 7 days (2
Overview
Basic Info.
Model NO. Zn83-24kv
Installation Fixed
Structure Withdrawable
Current AC
Clearance Between Open Contacts 12~14 mm
Mechanical Life (M2) 10,000(20,000)Times
Contact Stroke 3~5mm
Rated Short-Circuit Breaking Current 20,25,31.5ka
Rated Peak Withstand Current 50,63,80ka
Transport Package Carton
Specification ZN83-24KV
Trademark VACEM
Origin Wenzhou, China
HS Code 85352100
Packaging & Delivery
Package Size 96.00cm * 31.00cm * 70.00cm Package Gross Weight 120.000kg Lead Time 3 days (1 - 1 pcs)
7 days (2 - 10 pcs)
30 days (11 - 100 pcs)
To be negotiated ( > 100 pcs)
Product Description

General description

The ZN83-24KV series VCB is an exciting new addition to the indoor switchgear lineup from VACEM Co., Ltd. Designed specifically for 24KV power systems, this cutting-edge product is sure to impress.
One of the standout features of the ZN83-24KV series is its optimized modular spring operating mechanism. This mechanism not only ensures high reliability but also boasts a long service life and requires minimal maintenance. With this innovative design, you can trust that your power system will be in safe hands.
The ZN83-24KV series vacuum circuit breaker is not just any ordinary switchgear. It serves as a powerful protection and control unit for power equipment in industrial and mining enterprises. What sets it apart is its ability to thrive in even the harshest environments, thanks to its frequent operation and multiple disconnection capabilities for short-circuits.

Experience the thrill of the ZN83-24KV series VCB and take your power system to new heights.Main technical parameter
ItemUnitDate
Rated voltagekV24
Rated frequencyHz50
Rated insulation level1min power frequency withstand voltagepole to earthkV65
phasekV79
lightning impulse withstand voltagepole to earthkV125
phasekV145
Power frequency withstand voltage of secondary circuitV2000
Rated currentA63063012501250
1250125016003150
2000
Rated short-circuit breaking currentkA202531.5
Rated short-time withstand currentkA202531.5
Rated short circuit durations
Rated peak withstand currentkA506380
Rated short-circuit making currentkA506380
Rated short-circuit current breaking time (classE2)times30
Rated single/back to back capacitor bank breaking currentA630/400
Clearance between open contactsmm12~14
Contact strokemm3~5
Allowable wear thickness of contactmm3
Average opening speedm/s1.1~1.6
Average closing speedm/s0.6~1.1
Contact closing bounce timems≤2
Different phase of contact closing and openingms≤2
Rebound amplitude of opening contactmm≤2
Opening time (rated voltage)ms20~50
Closing time (rated voltage)ms30~70
Mechanical life (M2)times10,000(20,000)
Rated operating voltageVAC110/220 DC110/220
Rated operation sequence 0-0.3s-CO-180s-CO

For more switchgear parts, pls refer to insulation parts: https://china-vacem.en.made-in-china.com/product-group/BbRAnYUjsLrW/Insulation-Accessories-catalog-1.html, or copper tulip contact: https://china-vacem.en.made-in-china.com/product-group/nbUGDIpPuLYM/Tulip-contact-series-1.htmlInternational fairs

24kv Indoor Medium Voltage Side Installation Type Vacuum Circuit Breaker

Company show

24kv Indoor Medium Voltage Side Installation Type Vacuum Circuit Breaker

24kv Indoor Medium Voltage Side Installation Type Vacuum Circuit Breaker

24kv Indoor Medium Voltage Side Installation Type Vacuum Circuit Breaker

24kv Indoor Medium Voltage Side Installation Type Vacuum Circuit Breaker